Three Phase EATON 9390 UPS
9390 20-80 kVA UPS
Three Phase EATON 9390 UPS
9390 small battery cabinet with doors open
Three Phase EATON 9390 UPS 2
9390 100-160 kVA inside view
Three Phase EATON 9390 UPS 3
9390 large battery cabinet with doors open
« »
EATON 9390 UPS

Formerly Powerware 9390 UPS
The energy-efficient Eaton 9390 UPS provides backup power and scalable battery runtimes in a small footprint for mid-size data centers, medical equipment and other critical systems. With the groundbreaking Energy Saver System, the 9390 operates at 99% UPS efficiency and can pay for itself in three to five years—without sacrificing reliability.

Features & Benefits

• Delivers 99% efficiency without sacrificing reliability using Energy Saver System.

• Provides stronger power performance with optimum generator sizing, PFC power supply compatibility, and via lowest THD that enhances compatibility with upstream power systems.

• Offers the highest reliability and availability with Powerware Hot Sync paralleling, superior battery management, inherent redundancy and a scalable architecture that adapts to increasing power requirements.

• Delivers robust manageability with superior control and connectivity and with a superior service offering.

• Works with the Intelligent Power Software Suite, which offers free monitoring, management and shutdown software ideal for protecting physical and virtual machines

EATON 9390 UPS
Power Rating 20-160 kVA
Voltage 208/208, 380/380, 400/400, 480/480 (standard) 600/600, 600/208, 480/208 (optional)
Frequency 55-65 Hz
Configuration Tower
Product Series Powerware
Technical Specifications for EATON 9390 UPS
UPS RATING (0.9 POWER FACTOR) :
kVA
kW
20 / 30 / 40 / 50 / 60 / 80 / 100 / 120 / 160
18 / 27 / 36 / 45 / 54 / 72 / 90 / 108 / 144
Efficiency Up to 98% High-efficiency mode, Up to 92% Double-conversion
GENERAL :
Efficiency Up to 94%>99% with Energy Saver System
Parallel capability 6x modules w/o tie cabinet; 8x with tie cabinet
Audible noise <65 dBA @ 1 meter
Altitude (max) 2000m at 40ºC , 104ºF
ELECTRICAL INPUT :
Voltage 208, 380, 400, 415, 480, 6002
Voltage range +10% / -15%3
Frequency range 55-65 Hz
Power factor 0.99 (min)
Input current distortion <4.5% (no input filter required)
Soft start capability Yes
Internal backfeed protection Yes
Broadcast global support Yes
ELECTRICAL OUTPUT :
Voltage 2084, 3804, 4004, 4154, 4804, 6005
Regulation ±1%
Inverter PWM with IGBT switching
Voltage THD <2% (100% linear load); <5% (non-linear load)
Load power factor range Down to 0.9pf leading without de-rating
Heat dissipation (BTU/Hr x 1000/Hr) 80 kVA, 208V: 23.6
160 kVA, 208V: 47.3
80 kVA, 380-480V: 21.9
160 kVA, 380-480V: 43.8
BATTERY :
Battery types VRLA, AGM, Gel, Wet, Eaton batteries also available
Battery voltage 384-480V
Temperature compensation Optional
Charging method Advanced battery management
Heat dissipation <48 BTU @ full load
DIMENSIONS AND WEIGHTS :
40-80 kVA modules
120-160 kVA modules
40-80 kVA modules
100-160 kVA modules
HxWxD: 73.7 x 18.9 x 31.6 in./1872 x 480 x 803 mm
HxWxD: 73.7 x 35.6 x 31.6 in./1872 x 904 x 803 mm
640 lb./290 kg (208V); 568 lb./258 kg (480V)
1,060 lb./481 kg (208V, 480V)
CERTIFICATION :
Safety UL1778, cUL
EMC IEC62040-2 EN50091 Class A (restricted access)
Surge ANSI C62, 41 Cat, A&B
OPTIONAL ACCESORIES :
Module tie cabinet
External maintenance bypass
Integrated distribution cabinet
Isolation transformer
1. Due to continuous product improvements, program specifications are subject to change without notice.