Three Phase EATON 93E UPS
40 and 60 kVA 93E come with internal batteries
Three Phase EATON 93E UPS 2
LCD graphic display uses easy-to-navigate buttons with LED status indicators
Three Phase EATON 93E UPS 3
93E graphic display allows easy-to-view UPS power flow diagrams with system alerts and messages
« »
EATON 93E UPS

Formerly EATON 9E
The Eaton 93E UPS delivers customers the most efficient power quality solution in three key areas: space, power and cost. Engineered for maximum efficiency, the 93E delivers up to 98% efficiency while maintaining a small physical footprint. With internal batteries up to 60 kVA, the 93E provides an all-in-one solution that also reduces the complexity of installation and startup and provides maximum runtime.

Features & Benefits

• Lower operating costs through 98% efficiency.

• Up to 21 minutes of runtime with internal batteries.

• Up to 138 minutes of runtime when paired with an Extended Battery Cabinet (EBC).

• Up to 35% smaller footprint than similar competitive solutions.

• One year parts and labor included with Eaton startup plan protection to the load.

• Intelligent Power Manager Software monitors and manages multiple power devices across your network.

• Single cabinet solution reduces installation, wiring, and maintenance costs.

• Detachable maintenance bypass options guarantee zero downtime.

EATON 93E UPS
Power Rating 20-60 kVA
Voltage 208/220 Vac three phase
Frequency 50/60 Hz
Configuration Tower
Technical Specifications for EATON 93E UPS
GENERAL :
Topology Double-conversion online
Configuration Tower
Rating (VA/Watts) 20 kVA/16 kW
Efficiency Up to 98% High-efficiency mode, Up to 92% Double-conversion
UPS Bypass Automatic on overload or UPS failure
Dimensions (H x W x D, inches)
Dimensions (H x W x D, mm)
53.5 x 20.9 x 31.5
1360 x 530 x 800
ELECTRICAL INPUT :
Connection Hardwired
Operating frequency 50/60 Hz (45 to 65 Hz)
Input power factor 0.99 typical
Input current distortion <5% THD
ELECTRICAL OUTPUT :
Nominal voltage 208/220, 3/4 wire
Output voltage regulation ±1% Static; ±5% dynamic at 100% resistive load change, <20 ms response time
Output Receptacles Hardwired - see manual for terminal block layout
Overload Capacity 150% for 40 ms / 125% for 30 seconds / 110% for 10 min
BATTERY :
Battery type 9 Ah, sealed, lead-acid, maintenance-free
Battery Management ABM (Cyclic) or float
Battery replacement Field-replaceable
Internal Batteries Yes, has internal batteries. Field service upgrades needed to add external batteries (EBCs) to extend runtime
COMMUNICATIONS :
User Interface Graphical LCD with blue backlight
LEDs (4) LEDs for notice and alarm
Audible alarms Yes
Communication ports (1) RS-232, (1) REPO
Communication slot (2) Mini-slot communication bays
Power management software Eaton Intelligent Power Software Suite CD
ENVIROMENTAL & Standards :
Audible Noise < 64 dBA at 1 meter (noise less room) typical
Operating Temperature 0ºC (32ºF) to +30ºC (86ºF); Batteries recommended max. +25ºC (77ºF)
Safety markings UL60950 , EN55022/EN55024
EMC Markings IEC 62040-2
Markings UL, cUL
Storage Temperature -25ºC (-13ºF) to +55ºC (131ºF) without batteries; +15ºC (59ºF) to +25ºC (77ºF) with batteries
Relative Humidity 5 –95%, non-condensing
Altitude < 1000m at +30°C (86ºF)
1. Due to continuous product improvements, program specifications are subject to change without notice.